Monitored Data - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

Section 8
Current protection
Name
Values (Range)
ResetTypeCrv4
Instantaneous
IEC Reset
ANSI reset
tReset4
0.000 - 60.000
tPCrv4
0.005 - 3.000
tACrv4
0.005 - 200.000
tBCrv4
0.00 - 20.00
tCCrv4
0.1 - 10.0
tPRCrv4
0.005 - 3.000
tTRCrv4
0.005 - 100.000
tCRCrv4
0.1 - 10.0
HarmBlock4
Disabled
Enabled
Table 95:
OC4PTOC (51_67) Non group settings (basic)
Name
Values (Range)
MeasType
DFT
RMS
GlobalBaseSel
1 - 12
8.1.6
178
Unit
Step
-
-
s
0.001
-
0.001
-
0.001
-
0.01
-
0.1
-
0.001
-
0.001
-
0.1
-
-
Unit
Step
-
-
-
1

Monitored data

Table 96:
OC4PTOC (51_67) Monitored data
Name
Type
DIR_A
INTEGER
DIR_B
INTEGER
DIR_C
INTEGER
Table continues on next page
Default
Description
Instantaneous
Selection of reset curve type for step 4
0.020
Constant reset time for step 4
1.000
Parameter P for customer programmable
curve for step 4
13.500
Parameter A for customer programmable
curve for step 4
0.00
Parameter B for customer programmable
curve for step 4
1.0
Parameter C for customer programmable
curve for step 4
0.500
Parameter PR for customer programmable
curve for step 4
13.500
Parameter TR for customer programmable
curve for step 4
1.0
Parameter CR for customer programmable
curve for step 4
Disabled
Enable block of step 4 from harmonic restrain
Default
Description
DFT
Selection between DFT and RMS
measurement
1
Selection of one of the Global Base Value
groups
Values (Range)
Unit
1=Forward
-
2=Reverse
0=No direction
1=Forward
-
2=Reverse
0=No direction
1=Forward
-
2=Reverse
0=No direction
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
PID-6973-MONITOREDDATA v3
Description
Direction for phase A
Direction for phase B
Direction for phase C
Technical manual