Section 17
Metering
598
Figure
238
shows the pulse-counter logic function block with connections of the inputs
and outputs.
SingleCmdFunc
OUTx
Pulse
SingleCmdFunc
OUTx
INPUT OUT
Pulse length >1s
I/O-
module
"Reset counter"
SMS settings
1.Operation = Off/On
2.tReporting = 0s...60min
3.Event Mask = No Events/Report Events
4.Scale = 1-90000
ANSI05000744 V1 EN-US
Figure 238:
Overview of the pulse-counter logic function
The BLOCK and READ_VAL inputs can be connected to Single Command logics,
which are intended to be controlled either from the station HMI or/and the local HMI.
As long as the BLOCK signal is set, the pulse counter is blocked. The signal connected
to READ_VAL performs one additional reading per positive flank. The signal must be
a pulse with a length >1 second.
The BI_PULSE input is connected to the used input of the function block for the
Binary Input Module (BIM).
The RS_CNT input is used for resetting the counter.
Each pulse-counter logic function block has four binary output signals that can be
connected to an Event function block for event recording: INVALID, RESTART,
BLOCKED and NEW_VAL. The SCAL_VAL signal can be connected to the IEC
Event function block.
The INVALID signal is a steady signal and is set if the Binary Input Module, where the
pulse counter input is located, fails or has wrong configuration.
The RESTART signal is a steady signal and is set when the reported value does not
comprise a complete integration cycle. That is, in the first message after IED pickup, in
the first message after deblocking, and after the counter has wrapped around during last
integration cycle.
PulseCounter
BLOCK
INVALID
RESTART
READ_VAL
BLOCKED
NEW_VAL
BI_PULSE
RS_CNT
NAME
SCAL_VAL
Database
Pulse counter value:
0...2147483647
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
M13399-3 v9
EVENT
INPUT1
INPUT2
INPUT3
INPUT4
IEC EVENT
en05000744_ansi.vsd
Technical manual

Advertisement

Table of Contents
loading

Table of Contents