Section 15
Logic
15.11.5
15.11.6
15.11.7
464
Table 335:
B16I Output signals
Name
Type
OUT
INTEGER

Monitored data

Table 336:
B16I Monitored data
Name
Type
OUT
INTEGER
Settings
The function does not have any parameters available in the local HMI or PCM600.
Operation principle
The Boolean 16 to integer conversion function (B16I) will transfer a combination of up
to 16 binary inputs INx, where 1≤x≤16, to an integer. Each INx represents a value
according to the table below from 0 to 32768. This follows the general formula: INx =
x-1
2
where 1≤x≤16. The sum of all the values on the activated INx will be available on
the output OUT as a sum of the integer values of all the inputs INx that are activated.
OUT is an integer. When all INx (where 1≤x≤16) are activated, that is = Boolean 1, it
corresponds to that integer 65535 is available on the output OUT. The B16I function is
designed for receiving up to 16 booleans input locally. If the BLOCK input is
activated, it will freeze the output at the last value.
Values of each of the different OUTx from function block B16I for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the output
OUT on the function block B16I
Name of input
Type
IN1
BOOLEAN
IN2
BOOLEAN
IN3
BOOLEAN
IN4
BOOLEAN
IN5
BOOLEAN
IN6
BOOLEAN
Table continues on next page
Description
Output value
Values (Range)
Unit
-
-
Default
Description
0
Input 1
0
Input 2
0
Input 3
0
Input 4
0
Input 5
0
Input 6
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
PID-3606-OUTPUTSIGNALS v3
PID-3606-MONITOREDDATA v4
Description
Output value
ABBD8E283673 v3
SEMOD175737-4 v5
Value when
Value when
activated
deactivated
1
0
2
0
4
0
8
0
16
0
32
0