Functionality

Insulation supervision for gas medium (SSIMG (63)) is used for monitoring the circuit
breaker condition. Binary information based on the gas pressure in the circuit breaker
is used as input signals to the function. In addition, the function generates alarms based
on received information.
Function block
SSIMG (63)
BLOCK
LOCKOU T
BLKALM
PRESLO
SENPRES
TEMPLO
SENTEMP
ALARM
SENPRESALM
PRESALM
SENPRESLO
TEMPALM
SETP LO
PRESSURE
SETTLO
TEMP
RESETLO
ANSI09000129-2-en.vsdx
ANSI09000129 V2 EN-US
Figure 204:
SSIMG (63) function block
Signals
Table 399:
SSIMG Input signals
Name
Type
BLOCK
BOOLEAN
BLKALM
BOOLEAN
SENPRES
REAL
SENTEMP
REAL
SENPRESALM
BOOLEAN
SENPRESLO
BOOLEAN
SETPLO
BOOLEAN
SETTLO
BOOLEAN
RESETLO
BOOLEAN
Default
Description
0
Block of function
0
Block all the alarms
0.0
Pressure input from CB
0.0
Temperature of the insulation medium from CB
0
Pressure alarm signal
0
Pressure lockout signal
0
Set pressure lockout
0
Set temperature lockout
0
Reset pressure and temperature lockout
Section 16
Monitoring
GUID-0692CD0D-F33E-4370-AC91-B216CAAAFC28 v6
GUID-94B75A6D-973D-4F1F-8643-F2128AD31CC4 v3
GUID-89749F71-CAEB-4A57-A1F0-148CCF68E97E v2
PID-6950-INPUTSIGNALS v6
525