Signals - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
16.10.4
16.10.5
Table 441:
TEILGAPC Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
tAlarm
1.0 - 99999.9
tWarning
1.0 - 99999.9
tAddToTime
0.0 - 99999.9
16.10.6
Phasor measurement unit RES670 2.2 ANSI
Technical manual

Signals

Table 439:
TEILGAPC Input signals
Name
Type
BLOCK
BOOLEAN
IN
BOOLEAN
ADDTIME
BOOLEAN
RESET
BOOLEAN
Table 440:
TEILGAPC Output signals
Name
Type
ALARM
BOOLEAN
WARNING
BOOLEAN
OVERFLOW
BOOLEAN
ACC_HOUR
REAL
ACC_DAY
REAL
Settings
Unit
Step
-
-
Hour
0.1
Hour
0.1
Hour
0.1
Operation principle
Figure
236
describes the simplified logic of the function.
Default
Description
0
Freeze the accumulation and block the outputs
0
The input signal that is used to measure the elapsed
time, when its value is high
0
Add time to the accumulation
0
Reset accumulated time
Description
Indicator that accumulated time has reached alarm
limit
Indicator that accumulated time has reached warning
limit
Indicator that accumulated time has reached overflow
limit
Accumulated time in hours
Accumulated time in days
Default
Description
Disabled
Operation Disabled/Enabled
90000.0
Time limit for alarm supervision
50000.0
Time limit for warning supervision
0.0
Time to add to the accumulation
Section 16
Monitoring
PID-6998-INPUTSIGNALS v1
PID-6998-OUTPUTSIGNALS v1
PID-6998-SETTINGS v1
GUID-C7F91D4E-5942-4006-B7C8-4F499E7DC49D v3