1MRK 511 408-UUS A
14.1.7.1
Phasor measurement unit RES670 2.2 ANSI
Technical manual
kept and further operation will be blocked. The operator place (local or remote) is
specified through the PSTO input. If any operation is allowed the signal INTONE from
the Fixed signal function block can be connected. SLGAPC function block has also an
integer value output, that generates the actual position number. The positions and the
block names are fully settable by the user. These names will appear in the menu, so the
user can see the position names instead of a number.
Graphical display
There are two possibilities for SLGAPC
•
if it is used just for the monitoring, the switches will be listed with their actual
position names, as defined by the user (max. 13 characters).
•
if it is used for control, the switches will be listed with their actual positions, but
only the first three letters of the name will be used.
In both cases, the switch full name will be shown, but the user has to redefine it when
building the Graphical Display Editor, under the "Caption". If used for the control, the
following sequence of commands will ensure:
Section 14
Control
SEMOD114931-35 v4
385