Circuit Breaker Gas Pressure Indication - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
16.4.7.8
Phasor measurement unit RES670 2.2 ANSI
Technical manual
SPRCHRST
SPRCHRD
RSTSPCHT
BLOCK
BLKALM
IEC12000621 V2 EN-US
Figure 216:
Functional module diagram for circuit breaker spring charge indication
Spring charging time measurement
Spring charging time calculation will be initiated as soon as the circuit breaker is
closed and charging motor starts (NO contact of the device is connected to SPRCHRST)
to store the energy in the close spring. An indicator provided in the circuit breaker is
displayed when the spring is completely charged. This status is taken through NO
contact and then connected to SPRCHRD.
The binary input SPRCHRST indicates the pickup of circuit breaker spring charging
time. SPRCHRD indicates that the circuit breaker spring is charged. The spring
charging time is calculated from the difference of these two signal timings. Spring
charging indication is described in figure 216.
The last measured spring charging time SPCHT is provided as a service value. The
spring charging time SPCHT can be reset on the LHMI or by activating the input
RSTSPCHT.
Alarm limit check
If the time taken by the spring to charge is more than the value set with the
SpChAlmTime setting, the subfunction generates the SPCHALM alarm.
It is possible to block the SPCHALM alarm signal by activating the BLKALM binary
input.

Circuit breaker gas pressure indication

The circuit breaker gas pressure indication subfunction monitors the gas pressure
inside the arc chamber. The operation is described in figure 217.
Spring charging
time
measurement
Alarm limit
Section 16
Monitoring
SPCHALM
Check
GUID-9D070D52-B499-4D45-9195-60181819184E v10
SPCHT
545