1MRK 511 408-UUS A
15.15.4
15.15.5
Table 351:
TEIGAPC Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
tWarning
1.00 - 999999.00
tAlarm
1.00 - 999999.00
15.15.6
Phasor measurement unit RES670 2.2 ANSI
Technical manual

Signals

Table 349:
TEIGAPC Input signals
Name
Type
BLOCK
BOOLEAN
IN
BOOLEAN
RESET
BOOLEAN
Table 350:
TEIGAPC Output signals
Name
Type
WARNING
BOOLEAN
ALARM
BOOLEAN
OVERFLOW
BOOLEAN
ACCTIME
REAL
Settings
Unit
Step
-
-
s
0.01
s
0.01
Operation principle
The elapsed time integrator (TEIGAPC) provides
time integration, accumulating the elapsed time when a given binary signal has
been high
blocking and reset of the total integrated time
supervision of limit transgression and overflow, the overflow limit is fixed to
999999.9 seconds
retaining of the integrated value
Default
Description
0
Freeze the integration and block the other outputs
0
The input signal that is used to measure the elapsed
time, when its value is high
0
Reset the integration time
Description
Indicator of the integrated time has reached the
warning limit
Indicator of the integrated time has reached the alarm
limit
Indicator of the integrated time has reached the
overflow limit
Integrated elapsed time in seconds
Default
Description
Disabled
Operation Disabled/Enabled
600.00
Time limit for warning supervision
1200.00
Time limit for alarm supervision
Section 15
Logic
PID-6836-INPUTSIGNALS v2
PID-6836-OUTPUTSIGNALS v2
PID-6836-SETTINGS v2
GUID-04CC8365-DCDE-4DC7-BEF0-6EF8382305DD v3
477