Table 487:
GOOSEMVRCV Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
Phasor measurement unit RES670 2.2 ANSI
Technical manual

Function block

GOOSEMVRCV
BLOCK
^MVOUT
^SRCMVOUT
DATAVALID
COMMVALID
TEST
IEC10000251-2-en.vsd
IEC10000251 V2 EN-US
Figure 258:
GOOSEMVRCV function block
Signals
Except for the BLOCK input, the rest of the inputs of this GOOSE
function block are used for GOOSE connections. These connections are
visible and possible to make only if Easy GOOSE engineering is
enabled. For instructions on how to enable Easy GOOSE engineering in
PCM600, refer to the Engineering Manual.
Table 485:
GOOSEMVRCV Input signals
Name
Type
BLOCK
BOOLEAN
SRCMVOUT
REAL
Table 486:
GOOSEMVRCV Output signals
Name
Type
MVOUT
REAL
DATAVALID
BOOLEAN
COMMVALID
BOOLEAN
TEST
BOOLEAN
Settings
Unit
Step
-
-
Station communication
Default
Description
0
Block of function
0
Source to measurand value output
Description
Measurand value output
Data valid for measurand value output
Communication valid for measurand value output
Test output
Default
Description
Disabled
Operation Disabled/Enabled
Section 19
GUID-A0B333CC-AEF4-40EA-B152-364648AB78D3 v1
GUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1
PID-6830-INPUTSIGNALS v3
PID-6830-OUTPUTSIGNALS v3
PID-6830-SETTINGS v3
639