17.2.4
Phasor measurement unit RES670 2.2 ANSI
Technical manual

Signals

Table 448:
ETPMMTR Input signals
Name
Type
P
REAL
Q
REAL
STARTACC
BOOLEAN
STOPACC
BOOLEAN
RSTACC
BOOLEAN
RSTDMD
BOOLEAN
Table 449:
ETPMMTR Output signals
Name
Type
ACCINPRG
BOOLEAN
EAFPULSE
BOOLEAN
EARPULSE
BOOLEAN
ERFPULSE
BOOLEAN
ERRPULSE
BOOLEAN
EAFALM
BOOLEAN
EARALM
BOOLEAN
ERFALM
BOOLEAN
ERRALM
BOOLEAN
EAFACC
REAL
EARACC
REAL
ERFACC
REAL
ERRACC
REAL
MAXPAFD
REAL
MAXPARD
REAL
MAXPRFD
REAL
MAXPRRD
REAL
Default
Description
0
Measured active power
0
Measured reactive power
0
Start to accumulate energy values
0
Stop accumulating energy values
0
Reset of accumulated enery reading
0
Reset of maximum demand reading
Description
Accumulation of energy values in progress
Accumulated forward active energy pulse
Accumulated reverse active energy pulse
Accumulated forward reactive energy pulse
Accumulated reverse reactive energy pulse
Alarm for active forward energy exceed limit in set
interval
Alarm for active reverse energy exceed limit in set
interval
Alarm for reactive forward energy exceed limit in set
interval
Alarm for reactive reverse energy exceed limit in set
interval
Accumulated forward active energy value
Accumulated reverse active energy value
Accumulated forward reactive energy value
Accumulated reverse reactive energy value
Maximum forward active power demand value for set
interval
Maximum reverse active power demand value for set
interval
Maximum forward reactive power demand value for
set interval
Maximum reverse reactive power demand value for
set interval
Section 17
Metering
PID-6872-INPUTSIGNALS v3
PID-6872-OUTPUTSIGNALS v3
601