Section 14
Control
14.2.5
Table 217:
VSGAPC Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
CtlModel
Dir Norm
SBO Enh
Mode
Steady
Pulsed
tSelect
0.000 - 60.000
tPulse
0.000 - 60.000
14.2.6
388

Settings

Unit
Step
-
-
-
-
-
-
s
0.001
s
0.001
Operation principle
Selector mini switch (VSGAPC) function can be used for double purpose, in the same
way as switch controller (SCSWI) functions are used:
for indication on the single line diagram (SLD). Position is received through the
IPOS1 and IPOS2 inputs and distributed in the configuration through the POS1
and POS2 outputs, or to IEC 61850 through reporting, or GOOSE.
for commands that are received via the local HMI or IEC 61850 and distributed in
the configuration through outputs CMDPOS12 and CMDPOS21.
The output CMDPOS12 is set when the function receives a CLOSE command
from the local HMI when the SLD is displayed and the object is chosen.
The output CMDPOS21 is set when the function receives an OPEN command
from the local HMI when the SLD is displayed and the object is chosen.
It is important for indication in the SLD that a symbol is associated
with a controllable object, otherwise the symbol won't be displayed on
the screen. A symbol is created and configured in GDE tool in
PCM600.
The PSTO input is connected to the Local remote switch to have a selection of
operators place, operation from local HMI (Local) or through IEC 61850 (Remote). An
INTONE connection from Fixed signal function block (FXDSIGN) will allow
operation from local HMI.
As it can be seen, both indications and commands are done in double-bit
representation, where a combination of signals on both inputs/outputs generate the
desired result.
Default
Description
Disabled
Operation Disabled/Enabled
Dir Norm
Specifies the type for control model according
to IEC 61850
Pulsed
Operation mode
30.000
Max time between select and execute signals
0.200
Command pulse lenght
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
PID-6504-SETTINGS v6
SEMOD158762-4 v6