Operation Principle - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

Section 22
Basic IED functions
Table 615:
SMAI2 Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 12
DFTReference
InternalDFTRef
DFTRefGrp1
DFTRefGrp2
DFTRefGrp3
DFTRefGrp4
DFTRefGrp5
DFTRefGrp6
DFTRefGrp7
DFTRefGrp8
DFTRefGrp9
DFTRefGrp10
DFTRefGrp11
DFTRefGrp12
External DFT ref
ConnectionType
Ph-N
Ph-Ph
AnalogInputType
Voltage
Current
Table 616:
SMAI2 Non group settings (advanced)
Name
Values (Range)
Negation
Disabled
NegateN
Negate3Ph
Negate3Ph+N
MinValFreqMeas
5 - 200
22.9.5
790
Unit
Step
-
1
-
-
-
-
-
-
Unit
Step
-
-
%
1

Operation principle

Every Signal matrix for analog inputs function (SMAI) can receive four analog signals
(three phases and one neutral or residual value), either voltage or current, see
figure
301
and figure 302. SMAI outputs give information about every aspect of the
3ph analog signals acquired (phase angle, RMS value, frequency and frequency
derivates etc. – 244 values in total). The BLOCK input will force all outputs to value
zero if BLOCK is TRUE (1).
System phase rotation and frequency are defined using the PhaseRotation and
Frequency settings in the primary system values PRIMVAL function. Logic 1 in the
REVROT input to the SMAI function means that the phase rotation is changed relative
to the set PhaseRotation in PRIMVAL.
Default
Description
1
Selection of one of the Global Base Value
groups
InternalDFTRef
DFT reference
Ph-N
Input connection type
Voltage
Analog input signal type
Default
Description
Disabled
Negation
10
Limit for frequency calculation in % of VBase
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
PID-3406-SETTINGS v5
SEMOD55746-4 v13
Technical manual