Settings - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
9.1.5
Table 150:
UV2PTUV (27) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
OperationStep1
Disabled
Enabled
Characterist1
Definite time
Inverse curve A
Inverse curve B
Prog. inv. curve
OpMode1
1 out of 3
2 out of 3
3 out of 3
Pickup1
1.0 - 100.0
t1
0.00 - 6000.00
t1Min
0.000 - 60.000
TD1
0.05 - 1.10
IntBlkSel1
Disabled
Block of trip
Block all
IntBlkStVal1
1 - 50
Table continues on next page
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Name
Type
TRST2_A
BOOLEAN
TRST2_B
BOOLEAN
TRST2_C
BOOLEAN
PICKUP
BOOLEAN
PU_ST1
BOOLEAN
PU_ST1_A
BOOLEAN
PU_ST1_B
BOOLEAN
PU_ST1_C
BOOLEAN
PU_ST2
BOOLEAN
PU_ST2_A
BOOLEAN
PU_ST2_B
BOOLEAN
PU_ST2_C
BOOLEAN

Settings

Unit
Step
-
-
-
-
-
-
-
-
%VB
0.1
s
0.01
s
0.001
-
0.01
-
-
%VB
1
Description
Trip signal from step2 phase A
Trip signal from step2 phase B
Trip signal from step2 phase C
Common pickup signal
Common pickup signal from step1
Pickup signal from step1 phase A
Pickup signal from step1 phase B
Pickup signal from step1 phase C
Common pickup signal from step2
Pickup signal from step2 phase A
Pickup signal from step2 phase B
Pickup signal from step2 phase C
Default
Description
Disabled
Operation Disabled/Enabled
Enabled
Enable execution of step 1
Definite time
Selection of time delay curve type for step 1
1 out of 3
Number of phases required for op (1 of 3, 2 of
3, 3 of 3) from step 1
70.0
Voltage pickup value (Definite-Time &
Inverse-Time curve) in % of VBase, step 1
5.00
Definitive time delay of step 1
5.000
Minimum operate time for inverse curves for
step 1
0.05
Time dial multiplier for the inverse time delay
for step 1
Disabled
Internal (low level) blocking mode, step 1
20
Voltage setting for internal blocking in % of
VBase, step 1
Section 9
Voltage protection
PID-3586-SETTINGS v7
273