Section 8
Current protection
8.6.5
Table 134:
GUPPDUP (37) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
OpMode1
Disabled
UnderPower
Power1
0.0 - 500.0
Angle1
-180.0 - 180.0
TripDelay1
0.01 - 6000.00
DropDelay1
0.01 - 6000.00
OpMode2
Disabled
UnderPower
Power2
0.0 - 500.0
Angle2
-180.0 - 180.0
TripDelay2
0.01 - 6000.00
DropDelay2
0.01 - 6000.00
Table 135:
GUPPDUP (37) Group settings (advanced)
Name
Values (Range)
TD
0.000 - 0.999
Hysteresis1
0.2 - 5.0
Hysteresis2
0.2 - 5.0
IMagComp5
-10.000 - 10.000
IMagComp30
-10.000 - 10.000
IMagComp100
-10.000 - 10.000
VMagComp5
-10.000 - 10.000
VMagComp30
-10.000 - 10.000
VMagComp100
-10.000 - 10.000
Table continues on next page
254

Settings

Unit
Step
-
-
-
-
%SB
0.1
Deg
0.1
s
0.01
s
0.01
-
-
%SB
0.1
Deg
0.1
s
0.01
s
0.01
Unit
Step
-
0.001
%SB
0.1
%SB
0.1
%
0.001
%
0.001
%
0.001
%
0.001
%
0.001
%
0.001
Default
Description
Disabled
Operation Disabled/Enabled
UnderPower
Operation mode for stage 1 Off / On
1.0
Stage 1 underpower setting in Angle1
direction in % of SBase
0.0
Characteristic angle for max power senistivity
stage 1
1.00
Trip delay for stage 1
0.06
Drop-off delay for stage 1
UnderPower
Operation mode for stage 2 Off / On
1.0
Power setting for stage 2 in % of SBase
0.0
Characteristic angle for max power senistivity
stage 2
1.00
Trip delay for stage 2
0.06
Drop-off delay for stage 2
Default
Description
0.000
Low pass filter coefficient for power
measurement, P and Q
0.5
Absolute hysteresis of stage 1 in % SBase
0.5
Absolute hysteresis of stage 2 in % SBase
0.000
Amplitude correction compensates current
error at 5% of Ir
0.000
Amplitude correction compensates current
error at 30% of Ir
0.000
Amplitude correction compensates current
error at 100% of Ir
0.000
Amplitude correction compensates voltage
error at 5% of Ur
0.000
Amplitude correction compensates voltage
error at 30% of Ur
0.000
Amplitude correction compensates voltage
error at 100% of Ur
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
PID-3709-SETTINGS v6
Technical manual