Section 23
IED hardware
23.5.5
872
Table 680:
Auxiliary DC supply voltage influence on functionality during operation
Dependence on
Ripple, in DC auxiliary voltage
Operative range
Auxiliary voltage dependence, operate
value
Interrupted auxiliary DC voltage
Interruption
interval
0–50 ms
0–∞ s
Restart time
Table 681:
Frequency influence (reference standard: IEC 60255–1)
Dependence on
Frequency dependence,
operate value
Harmonic frequency
dependence (20% content)

Type tests according to standard

Table 682:
Electromagnetic compatibility
Test
1 MHz Oscillatory burst
disturbance
100 kHz slow damped oscillatory
wave immunity test
Ring wave immunity test, 100
kHz
Surge withstand capability test
Electrostatic discharge
Direct application
Indirect application
Electrostatic discharge
Direct application
Indirect application
Fast transient disturbance
Table continues on next page
Reference value
max. 2%
Full wave rectified
Within nominal range
f
±2.5 Hz for 50 Hz
n
f
±3.0 Hz for 60 Hz
n
nd
rd
th
2
, 3
and 5
harmonic of f
n
Type test values
2.5 kV
2.5 kV
2-4 kV
2.5 kV, oscillatory
4.0 kV, fast transient
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
4 kV
(SFP galvanic RJ45: 2kV)
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
Within nominal range Influence
15% of EL
0.01%/%
±20% of EL
0.01%/%
24-60 V DC ± 20%
100-250 V DC
±20%
No restart
Correct behaviour
at power down
< 300 s
Influence
±1.0%/Hz
±2.0%
Reference standards
IEC 60255-26
IEC 61000-4-18, Class III
IEC 61000-4-12, Class IV
IEEE/ANSI C37.90.1
IEC 60255-26
IEC 61000-4-2, Class IV
IEEE/ANSI C37.90.1
IEC 60255-26, Zone A
Technical manual
IP16288-1 v1