1MRK 511 408-UUS A
8.4.3
8.4.4
Phasor measurement unit RES670 2.2 ANSI
Technical manual

Function block

SDEPSDE (67N)
I3P*
TRIP
V3P*
TRDIRIN
BLOCK
TRNDIN
BLKTR
TRVN
BLKTRDIR
PICKUP
BLKNDN
PUDIRIN
BLKVN
PUNDIN
PUVN
PUFW
PUREV
CND
VNREL
ANSI07000032-2-en.vsd
ANSI07000032 V2 EN-US
Figure 70:
SDEPSDE (67N) function block
Signals
Table 113:
SDEPSDE (67N) Input signals
Name
Type
I3P
GROUP
SIGNAL
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKTR
BOOLEAN
BLKTRDIR
BOOLEAN
BLKNDN
BOOLEAN
BLKVN
BOOLEAN
Table 114:
SDEPSDE (67N) Output signals
Name
Type
TRIP
BOOLEAN
TRDIRIN
BOOLEAN
TRNDIN
BOOLEAN
TRVN
BOOLEAN
PICKUP
BOOLEAN
PUDIRIN
BOOLEAN
PUNDIN
BOOLEAN
PUVN
BOOLEAN
Table continues on next page
Default
Description
-
Group signal for current
-
Group signal for voltage
0
Blocks all the outputs of the function
0
Blocks the trip outputs of the function
0
Blocks the directional operate outputs of the function
0
Blocks the Non directional current residual outputs
0
Blocks the Non directional voltage residual outputs
Description
General trip of the function
Trip of the directional residual over current function
Trip of non directional residual over current
Trip of non directional residual over voltage
General pickup of the function
Pickup of the directional residual over current function
Pickup of non directional residual over current
Pickup of non directional residual over voltage
Section 8
Current protection
SEMOD172780-4 v6
PID-3892-INPUTSIGNALS v7
PID-3892-OUTPUTSIGNALS v7
231