Internal Signals - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
21.5.5.1
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Individual error signals from I/O modules can be obtained from respective module in
the Signal Matrix tool. Error signals from time synchronization can be obtained from
the INTERRSIG function block via two outputs TSYNCERR and RTCERR .

Internal signals

Self supervision provides several status signals that give information about the internal
status of the IED. For this reason they are also called internal signals. These internal
signals , available on local HMI under Main menu/Diagnostics/IED status/General,
can be divided into two groups.
Standard signals are always presented in the IED, see table 582.
Hardware dependent internal signals are collected depending on the hardware
configuration, see table 583.
Table 582:
Self-supervision's standard internal signals
Name of signal
Description
FAIL
Internal
Fail status
WARNING
Internal
Warning
status
RTCERROR
Real Time
Clock
status
TIMESYNCHERROR
Time
Synchroniz
ation
status
RTEERROR
Runtime
Execution
Error
status
IEC61850ERROR
IEC 61850
Error
status
DNP3
DNP3
error
status
LMDERROR
LON/Mip
Device
Error
status
Table continues on next page
Displayed on
Reasons for activation
local HMI as
Internal fail
This signal will be active if one or more of the
following internal signals are active; LMDERROR,
WATCHDOG, APPERROR, RTEERROR, or any
of the HW dependent signals
Internal
This signal will be active if one or more of the
warning
following internal signals are active; RTCERROR,
IEC61850ERROR
Real time
This signal will be active when there is a hardware
clock
error with the real time clock.
Time synch
This signal will be active when the source of the
time synchronization is lost, or when the time
system has to make a time reset.
Runtime
This signal will be active if the Runtime Engine
execution
failed to do some actions with the application
threads. The actions can be loading of settings or
parameters for components, changing of setting
groups, loading or unloading of application threads.
IEC61850
This signal will be active if the IEC 61850 stack did
not succeed in some actions like reading IEC
61850 configuration, startup, for example
DNP3
This signal will be active when DNP3 detects any
configuration error during startup.
SLM301
LON network interface, MIP/DPS, is in an
unrecoverable error state.
Section 21
Security
M11401-173 v9
755