ABB RES670 Technical Manual page 503

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
Name
Values (Range)
FrRepTyp
Cyclic
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
Operation
Disabled
Enabled
GlobalBaseSel
1 - 12
Mode
A, B, C
Arone
Pos Seq
AB
BC
CA
A
B
C
PowMagFact
0.000 - 6.000
PowAngComp
-180.0 - 180.0
k
0.000 - 1.000
Table 376:
CVMMXN Non group settings (advanced)
Name
Values (Range)
SDbRepInt
1 - 100000
SZeroDb
0 - 100000
SHiHiLim
0.0 - 2000.0
SHiLim
0.0 - 2000.0
SLimHyst
0.000 - 100.000
PDbRepInt
1 - 100000
PZeroDb
0 - 100000
PHiHiLim
-2000.0 - 2000.0
PHiLim
-2000.0 - 2000.0
PLowLim
-2000.0 - 2000.0
PLowLowLim
-2000.0 - 2000.0
PLimHyst
0.000 - 100.000
Table continues on next page
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Unit
Step
Default
-
-
Cyclic
-
-
Disabled
-
1
1
-
-
A, B, C
-
0.001
1.000
Deg
0.1
0.0
-
0.001
0.000
Unit
Step
Default
Type
1
10
m%
500
1000
%SB
0.1
150.0
%SB
0.1
120.0
%
0.001
5.000
Type
1
10
m%
500
1000
%SB
0.1
150.0
%SB
0.1
120.0
%SB
0.1
-120.0
%SB
0.1
-150.0
%
0.001
5.000
Section 16
Monitoring
Description
Reporting type
Operation Disabled/Enabled
Selection of one of the Global Base Value
groups
Selection of measured current and voltage
Magnitude factor to scale power calculations
Angle compensation for phase shift between
measured I & V
Low pass filter coefficient for power
measurement, V and I
Description
Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
Magnitude zero point clamping in 0,001% of
range
High High limit in % of SBase
High limit in % of SBase
Hysteresis value in % of range, common for
all limits
Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
Magnitude zero point clamping in 0,001% of
range
High High limit in % of SBase
High limit in % of SBase
Low limit in % of SBase
Low Low limit in % of SBase
Hysteresis value in % of range, common for
all limits
497