Section 20
Remote communication
20.1.4
Table 562:
LDCMRecBinStat1 Non group settings (basic)
Name
Values (Range)
ChannelMode
Blocked
Normal
OutOfService
TerminalNo
0 - 255
RemoteTermNo
0 - 255
CommSync
Slave
Master
OptoPower
LowPower
HighPower
ComAlarmDel
5 - 10000
ComAlrmResDel
5 - 10000
Table 563:
LDCMRecBinStat2 Non group settings (basic)
Name
Values (Range)
ChannelMode
Blocked
Normal
OutOfService
TerminalNo
0 - 255
RemoteTermNo
0 - 255
DiffSync
Echo
GPS
GPSSyncErr
Block
Echo
CommSync
Slave
Master
OptoPower
LowPower
HighPower
TransmCurr
CT-GRP1
CT-GRP2
CT-SUM
CT-DIFF1
CT-DIFF2
ComAlarmDel
5 - 10000
Table continues on next page
732

Settings

Unit
Step
-
-
-
1
-
1
-
-
-
-
ms
5
ms
5
Unit
Step
-
-
-
1
-
1
-
-
-
-
-
-
-
-
-
-
ms
5
Default
Description
Normal
Channel mode of LDCM
0
Terminal number used for line differential
communication
0
Terminal number on remote terminal
Slave
Com Synchronization mode of LDCM
LowPower
Transmission power for LDCM
100
Time delay before communication alarm
signal is activated
100
Reset delay before communication alarm
signal is reset
Default
Description
Normal
Channel mode of LDCM
0
Terminal number used for line differential
communication
0
Terminal number on remote terminal
Echo
Diff Synchronization mode of LDCM
Block
Operation mode when GPS synchroniation
signal is lost
Slave
Com Synchronization mode of LDCM
LowPower
Transmission power for LDCM
CT-GRP1
Summation mode for transmitted current
values
100
Time delay before communication alarm
signal is activated
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
PID-6471-SETTINGS v2
PID-6472-SETTINGS v2
Technical manual