Two types of directional measurement principles are available, I & V and IcosPhi&V.
The first principle, referred to as "I & V" in the parameter setting tool, checks that:
the magnitude of the measured current is bigger than the set pick-up level
the phasor of the measured current is within the operating region (defined by the
relay trip angle, ROADir parameter setting; see figure 114).
RCADir
Ipickup
ROADir
Operate region
IEC05000252-ANIS V1 EN-US
Figure 114:
I & V directional operating principle for CVGAPC function
where:
RCADir is 75°
ROADir is 50°
The second principle, referred to as "IcosPhi&V" in the parameter setting tool, checks
that:
that the product I·cos(Φ) is bigger than the set pick-up level, where Φ is angle
between the current phasor and the mta line
that the phasor of the measured current is within the operating region (defined by
the I·cos(Φ) straight line and the relay trip angle, ROADir parameter setting; see
figure 114).
V=-3V0
I=3Io
mta line
en05000252_anis.vsd
Section 11
Multipurpose protection
341