magnitude of polarizing voltage must be bigger than a minimum level defined by
setting VpolMin.
Note that –V2 is used to determine the location of the fault. This ensures the required
inversion of the polarizing voltage within the function.

External polarizing for negative sequence function

The individual steps within the protection can be set as non-directional. When this
setting is selected it is then possible via function binary input BLKx (where x indicates
the relevant step within the protection) to provide external directional control (that is,
torque control) by for example using one of the following functions if available in the
IED:
Distance protection directional function
Negative sequence polarized general current and voltage multi purpose protection
function
Internal negative sequence protection structure
The protection is internally divided into the following parts:
Four negative sequence overcurrent steps
Directional supervision element for negative sequence overcurrent steps with
integrated directional comparison step for communication based negative
sequence protection schemes (permissive or blocking)
Each part is described separately in the following sections.
Four negative sequence overcurrent stages
Each overcurrent stage uses Operating Quantity I2 (negative sequence current) as
measuring quantity. Every of the four overcurrent stage has the following built-in
facilities:
Operating mode (Disabled/ Non-directional /Forward / Reverse). By this
parameter setting the operating mode of the stage is selected. Note that the
directional decision (Forward/Reverse) is not made within the overcurrent stage
itself. The direction of the fault is determined in common "Directional Supervision
Element" described in the next paragraph.
Negative sequence current pickup value.
Type of operating characteristic (Inverse or Definite Time). By this parameter
setting it is possible to select Inverse or definite time delay for negative sequence
overcurrent function. Most of the standard IEC and ANSI inverse characteristics
Section 8
Current protection
GUID-21930E81-1B40-4BA4-B1D8-3B365327AEF6 v1