ABB RES670 Technical Manual page 163

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
Table 86:
OOSPPAM (78) Group settings (advanced)
Name
Values (Range)
NoOfSlipsZ1
1 - 20
NoOfSlipsZ2
1 - 60
tReset
1.000 - 60.000
Table 87:
OOSPPAM (78) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 12
ForwardR
0.00 - 1000.00
ForwardX
0.00 - 1000.00
ReverseR
0.00 - 1000.00
ReverseX
0.00 - 1000.00
InvertCTCurr
No
Yes
Table 88:
OOSPPAM (78) Non group settings (advanced)
Name
Values (Range)
pick up Angle
90.0 - 130.0
TripAngle
15.0 - 90.0
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Unit
Step
Default
-
1
1
-
1
3
s
0.001
6.000
Unit
Step
Default
-
1
1
%ZB
0.01
1.00
%ZB
0.01
10.00
%ZB
0.01
1.00
%ZB
0.01
10.00
-
-
No
Unit
Step
Default
Deg
0.1
110.0
Deg
0.1
60.0
Impedance protection
Description
Number of pole-slips in zone 1 required for
zone 1 trip
Number of pole-slips in zone 2 required for
zone 2 trip
Time without any slip required to completely
reset function
Description
Selection of one of the Global Base Value
groups
Real part of total forward impedance for Z2, in
% of VBase/(sqrt(3)*IBase)
Imag. part of total forward impedance for Z2,
in % of VBase/(sqrt(3)*IBase)
Real part of source impedance behind relay,
in % of VBase/(sqrt(3)*IBase)
Imag. part of source impedance behind relay,
in % of VBase/(sqrt(3)*IBase)
Invert current direction
Description
Angle between two rotors to get the pick up
signal, in deg
Maximum rotor angle to allow trip signals, in
deg
Section 7
157