Phasor measurement unit RES670 2.2 ANSI
Technical manual

Operation principle

The logic for group alarm ALMCALH block is provided with 16 input signals and one
ALARM output signal. The function block incorporates internal logic OR gate in order
to provide grouping of connected input signals to the output ALARM signal from the
function block.
When any one of 16 input signals (INPUT1 to INPUT16) has logical value 1, the
ALARM output signal will get logical value 1.
The function has a drop-off delay of 200 ms when all inputs are reset to provide a
steady signal.
Input 1
1
ANSI13000191 V1 EN-US
Figure 157:
Group alarm logic
Technical data
Table 245:
Number of ALMCALH instances
Function
3 ms
ALMCALH
-
Logic for group warning WRNCALH
Identification
Function description
Logic for group warning
200 ms
0
Quantity with cycle time
8 ms
-
IEC 61850
IEC 60617
identification
identification
WRNCALH
-
Section 15
Logic
GUID-0405BB7B-7EF7-4546-92CD-F703AA0DD9F4 v2
ALARM
ANSI13000191-1-en.vsd
GUID-A05AF26F-DC98-4E62-B96B-E75D19F20767 v1
100 ms
5
GUID-3EBD3D5B-F506-4557-88D7-DFC0BD21C690 v4
ANSI/IEEE C37.2
device number
-
425