Settings - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
8.5.5
Table 125:
LCPTTR (26) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
TRef
0 - 300
IRef
0 - 400
IMult
1 - 5
Tau
1 - 1000
AlarmTemp
0 - 200
Table continues on next page
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Name
Type
MULTPU
BOOLEAN
AMBTEMP
REAL
SENSFLT
BOOLEAN
RESET
BOOLEAN
Table 123:
LCPTTR (26) Output signals
Name
Type
TRIP
BOOLEAN
BFI_3P
BOOLEAN
ALARM
BOOLEAN
LOCKOUT
BOOLEAN
Table 124:
LFPTTR (26) Output signals
Name
Type
TRIP
BOOLEAN
BFI_3P
BOOLEAN
ALARM
BOOLEAN
LOCKOUT
BOOLEAN

Settings

Unit
Step
-
-
Deg C
1
%IB
1
-
1
Min
1
Deg C
1
Default
Description
0
Current multiplyer used when THOL is for two or more
lines
0
Ambient temperature from external temperature
sensor
0
Validity status of ambient temperature sensor
0
Reset of internal thermal load counter
Description
Trip
Pickup Signal
Alarm signal
Lockout signal
Description
Trip
Pickup Signal
Alarm signal
Lockout signal
Default
Description
Disabled
Operation Disabled/Enabled
90
Final temperature rise above ambient of the
line when loaded with IRef
100
The load current (in % of IBase) leading to
TRef temperature
1
Current multiplier when function is used for
two or more lines
45
Time constant of the line in minutes.
80
Temperature level for pickup (alarm)
Section 8
Current protection
PID-3908-OUTPUTSIGNALS v7
PID-3909-OUTPUTSIGNALS v8
PID-3908-SETTINGS v7
245