Section 17
Metering
17.2.2
17.2.3
600

Functionality

Power system measurement (CVMMXN) can be used to measure active as well as
reactive power values. Function for energy calculation and demand handling
(ETPMMTR) uses measured active and reactive power as input and calculates the
accumulated active and reactive energy pulses, in forward and reverse direction.
Energy values can be read or generated as pulses. Maximum demand power values are
also calculated by the function. This function includes zero point clamping to remove
noise from the input signal. As output of this function: periodic energy calculations,
integration of energy values, calculation of energy pulses, alarm signals for limit
violation of energy values and maximum power demand, can be found.
The values of active and reactive energies are calculated from the input power values
by integrating them over a selected time tEnergy. The integration of active and reactive
energy values will happen in both forward and reverse directions. These energy values
are available as output signals and also as pulse outputs. Integration of energy values
can be controlled by inputs (STARTACC and STOPACC) and EnaAcc setting and it can
be reset to initial values with RSTACC input.
The maximum demand for active and reactive powers are calculated for the set time
interval tEnergy and these values are updated every minute through output channels.
The active and reactive maximum power demand values are calculated for both
forward and reverse direction and these values can be reset with RSTDMD input.
Function block
ETPMMTR
P*
ACCINPRG
Q*
EAFPULSE
STARTACC
EARPULSE
STOPACC
ERFPULSE
RSTACC
ERRPULSE
RSTDMD
EAFALM
EARALM
ERFALM
ERRALM
EAFACC
EARACC
ERFACC
ERRACC
MAXPAFD
MAXPARD
MAXPRFD
MAXPRRD
IEC14000019-1-en.vsd
IEC14000019 V1 EN-US
Figure 239:
ETPMMTR function block
1MRK 511 408-UUS A
GUID-6898E29B-DA70-421C-837C-1BBED8C63A7A v3
Phasor measurement unit RES670 2.2 ANSI
Technical manual