there are several out-of-step relays in the power system, then the one which finds the
center of oscillation in its zone 1 should operate first.
Two current channels I3P1 and I3P2 are available in OOSPPAM function to allow the
direct connection of two groups of three-phase currents; that may be needed for very
powerful generators, with stator windings split into two groups per phase, when each
group is equipped with current transformers. The protection function performs a simple
summation of the currents of the two channels I3P1 and I3P2.

Function block

OOSPPAM (78)
I3P1*
TRIP
I3P2*
TRIPZ1
V3P*
TRIPZ2
BLOCK
PICKUP
BLKGEN
GENMODE
BLKMOT
MOTMODE
EXTZ1
R
X
SLIPFREQ
ROTORANG
VCOSPHI
ANSI14000055-1-en.vsd
ANSI12000188 V2 EN-US
Figure 41:
OOSPPAM (78) function block
Signals
Table 83:
OOSPPAM (78) Input signals
Name
Type
I3P1
GROUP
SIGNAL
I3P2
GROUP
SIGNAL
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKGEN
BOOLEAN
BLKMOT
BOOLEAN
EXTZ1
BOOLEAN
Impedance protection
Default
Description
-
Group connection for three-phase current input 1
-
Group connection for three-phase current input 2
-
Group connection for three-phase voltage input
0
Block of function
0
Block operation in generating direction
0
Block operation in motor direction
0
Extension of zone1 reach to zone2 settings
Section 7
GUID-CB98C615-8A93-438D-9DF0-542F333198AC v4
PID-3539-INPUTSIGNALS v10
155