1MRK 511 408-UUS A
15.1.5
Table 232:
SMPPTRC Group settings (basic)
Name
Values (Range)
Operation
Off
On
Program
3 phase
1ph/3ph
1ph/2ph/3ph
tTripMin
0.000 - 60.000
tWaitForPHS
0.020 - 0.500
Table 233:
SMPPTRC Group settings (advanced)
Name
Values (Range)
TripLockout
Off
On
AutoLock
Off
On
tEvolvingFault
0.000 - 60.000
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Table 231:
SMPPTRC Output signals
Name
Type
TRIP
BOOLEAN
TRL1
BOOLEAN
TRL2
BOOLEAN
TRL3
BOOLEAN
TR1P
BOOLEAN
TR2P
BOOLEAN
TR3P
BOOLEAN
CLLKOUT
BOOLEAN
START
BOOLEAN
STL1
BOOLEAN
STL2
BOOLEAN
STL3
BOOLEAN
STN
BOOLEAN
FW
BOOLEAN
REV
BOOLEAN

Settings

Unit
Step
-
-
-
-
s
0.001
s
0.001
Unit
Step
-
-
-
-
s
0.001
Description
General trip output signal
Trip signal from phase L1
Trip signal from phase L2
Trip signal from phase L3
Trip single-pole
Trip two-pole
Trip three-pole
Circuit breaker lockout output (set until reset)
General start signal
Start signal from phase L1
Start signal from phase L2
Start signal from phase L3
Start signal from neutral
General forward signal
General reverse signal
Default
Description
Off
Operation Off / On
1ph/3ph
Three ph; single or three ph; single, two or
three ph trip
0.150
Minimum duration of trip output signal
0.050
Secure 3-pole trip when phase selection
failed
Default
Description
Off
Latch TRIP output when SETLKOUT input is
activated
Off
Activate CLLKOUT output when TRIP output
is activated
2.000
Secure 3-pole tripping at evolving faults
Section 15
Logic
GUID-D6B3DFE3-F7DF-4602-B57E-764DC9EB0D4A v1
GUID-6D6424B9-B676-4D9B-949A-33C74BDC5711 v1
403

Advertisement

Table of Contents
loading