Phasor measurement unit RES670 2.2 ANSI
Technical manual
It is possible to create functionality with more than one frequency band limit by using
multiple instances of the function. This can be achieved by a proper configuration
based on the turbine manufacturer specification.

Function block

FTAQFVR (81A)
I3P*
ERROR
V3P*
TRIP
BLOCK
TRIPACC
CBCLOSE
TRIPCONT
CBOPEN
BFI_3P
LOADINIT
ACCALARM
HOLDACC
STRORHLD
RESETACC
FREQOK
VOLTOK
ANSI14000049-1-en.vsd
ANSI14000023 V1 EN-US
Figure 111:
FTAQFVR (81A) function block
Signals
Table 177:
FTAQFVR (81A) Input signals
Name
Type
I3P
GROUP
SIGNAL
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
CBCLOSE
BOOLEAN
CBOPEN
BOOLEAN
LOADINIT
BOOLEAN
HOLDACC
BOOLEAN
RESETACC
BOOLEAN
Table 178:
FTAQFVR (81A) Output signals
Name
Type
ERROR
BOOLEAN
TRIP
BOOLEAN
TRIPACC
BOOLEAN
Table continues on next page
Default
Description
-
Group signal for three phase current
-
Group signal for three phase voltage
0
Block of function
0
Circuit breaker closed status input
0
Circuit breaker open status input
0
Loads the initial accumulation time to the function
0
Holds the time accumulation when input is activated
0
Resetting the accumulated time of the function block
Description
Error output for incorrect settings
Trip signal of the function
Trip signal when accumulation time is exceeded the
set limit
Section 10
Frequency protection
GUID-E3D2093B-8A97-4037-AAFE-5483489BF350 v2
PID-6515-INPUTSIGNALS v4
PID-6515-OUTPUTSIGNALS v4
319