Goose Function Block To Receive An Integer Value Gooseintrcv - ABB Relion 670 Series RES670 Technical Manual

Phasor measurement unit 2.1 ansi
Table of Contents

Advertisement

1MRK 511 365-UUS A
18.10
18.10.1
18.10.2
18.10.3
18.10.4
Phasor measurement unit RES670 2.1 ANSI
Technical manual
GOOSE function block to receive an integer value
GOOSEINTRCV
Identification
Function description
GOOSE function block to receive an
integer value
Functionality
GOOSEINTRCV is used to receive an integer value using IEC61850 protocol via
GOOSE.
Function block
GOOSEINTRCV
BLOCK
^INTOUT
DATAVALID
COMMVALID
TEST
IEC10000250-1-en.vsd
IEC10000250 V1 EN
Figure 258:
GOOSEINTRCV function block
Signals
Table 553:
GOOSEINTRCV Input signals
Name
Type
BLOCK
BOOLEAN
Table 554:
GOOSEINTRCV Output signals
Name
Type
INTOUT
INTEGER
DATAVALID
BOOLEAN
COMMVALID
BOOLEAN
TEST
BOOLEAN
Station communication
IEC 61850
IEC 60617
identification
identification
GOOSEINTRCV
-
Default
Description
0
Block of function
Description
Integer output
Data valid for integer output
Communication valid for integer output
Test output
Section 18
ANSI/IEEE C37.2
device number
-
677