Section 19
Station communication
19.4.6.2
19.4.6.3
19.4.6.4
Table 477:
MVGAPC Non group settings (basic)
Name
Values (Range)
BasePrefix
micro
milli
unit
kilo
Mega
Giga
Tera
MV db
1 - 100000
MV zeroDb
0 - 100000
MV hhLim
-5000.00 - 5000.00
MV hLim
-5000.00 - 5000.00
Table continues on next page
632

Function block

MVGAPC
BLOCK
^VALUE
^IN
RANGE
IEC14000022-1-en.vsd
IEC14000022 V1 EN-US
Figure 255:
MVGAPC function block
Signals
Table 475:
MVGAPC Input signals
Name
Type
BLOCK
BOOLEAN
IN
REAL
Table 476:
MVGAPC Output signals
Name
Type
VALUE
REAL
RANGE
INTEGER
Settings
Unit
Step
-
-
Type
1
m%
500
xBase
0.01
xBase
0.01
Default
Description
0
Block of function
0
Analog input value
Description
Magnitude of deadband value
Range
Default
Description
unit
Base prefix (multiplication factor)
10000
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
1000
Zero point clamping in 0.001% of range
900.00
High High limit multiplied with the base prefix
(multiplication factor)
800.00
High limit multiplied with the base prefix
(multiplication factor)
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
SEMOD54712-4 v4
SEMOD55948-1 v2
PID-6753-INPUTSIGNALS v1
PID-6753-OUTPUTSIGNALS v1
SEMOD55954-1 v2
PID-6753-SETTINGS v1