Section 16
Monitoring
592
tWarning
tAlarm
BLOCK
RESET
IN
ADDTIME
tAddToTime
IEC15000322 V1 EN-US
Figure 236:
TEILGAPC Simplified logic
TEILGAPC main functionalities
IN: Accumulation of the elapsed time when input IN is high
applicable to very long time accumulation (≤99999.9 hours)
output ACC_HOUR presents accumulated value in hours and ACC_DAY
presents accumulated value in days
accumulated value is retained in a non-volatile memory
any retained value is used as initiation value for the integration following by
a restart
RESET: Reset of the accumulated value. Consequently all other outputs are also
reset
independent of the input IN value
reset the value of the nonvolatile memory to zero.
Note that the nonvolatile memory will not reset to zero if the input IN is high
during the reset.
reset can be made by activation of input RESET or from LHMI or with IEC
61850 command
ADDTIME: Manually add time to the currently accumulated time
Loop Delay
Transgression Supervision
Plus Retain
Time Accumulation
Loop Delay
1MRK 511 408-UUS A
OVERFLOW
WARNING
ALARM
ACC_HOUR
ACC_DAY
IEC15000322.vsd
Phasor measurement unit RES670 2.2 ANSI
Technical manual