Section 15
Logic
15.1.7
410
IntToBits
CND
BFI_3P
in
b0
FW
b1
REV
b2
BFI_A
b3
FW_A
b4
REV_A
b5
BFI_B
b6
FW_B
b7
REV_B
b8
BFI_C
b9
FW_C
b10
REV_C
b11
BFI_3P
b0 =
b1 = FW
b2 = REV
b3 = BFI_A
b4 = FW_A
b5 = REV_A
b6 = BFI_B
b7 = FW_B
b8 = REV_B
b9 = BFI_C
b10 = FW_C
b11 = REV_C
ANSI16000179 V2 EN-US
Figure 148:
The directional logic

Technical data

Table 234:
SMPPTRC (94) technical data
Function
Trip action
Minimum trip pulse length
3-pole trip delay
Evolving fault delay
BitsToInt
b0
out
b1
BitsToInt
b0
out
AND
b1
XOR
AND
BitsToInt
AND
b0
out
b1
XOR
AND
BitsToInt
AND
b0
out
b1
XOR
AND
Range or value
3-ph, 1/3-ph, 1/2/3-ph
(0.000-60.000) s
(0.020-0.500) s
(0.000-60.000) s
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
BFI_3P
BFI_A
BFI_B
BFI_C
FW
dirGeneral (61850
Standard)
0 = unknown
DIR
1 = forward
2 = backward (reverse)
3 = both
REV
dirPhsA (61850 Standard, phase
wize)
DIRL1
0 = unknown
1 = forward
2 = backward (reverse)
dirPhsB (61850 Standard, phase
wize)
DIRL2
0 = unknown
1 = forward
2 = backward (reverse)
dirPhsC (61850 Standard, phase
wize)
DIRL3
0 = unknown
1 = forward
2 = backward (reverse)
ANSI16000179=1=en=Original.vsdx
M12380-1 v12
Accuracy
-
±0.2% or ±15 ms whichever is
greater
±0.2% or ±15 ms whichever is
greater
±0.2% or ±15 ms whichever is
greater
Technical manual