Technical data

Table 294:
Number of ANDQT instances
Logic block
3 ms
ANDQT
-
Single point indication related signals combining function
block INDCOMBSPQT
The value of single point input (SP_IN) is copied to the value part of the SP_OUT
output. The TIME input is copied to the time part of the SP_OUT output. State input
bits are copied to the corresponding state part of the SP_OUT output. If the state or
value on the SP_OUT output changes, the Event bit in the state part is toggled.
INDCOMBSPQT can propagate the quality, the value and the time stamps of the
signals via IEC 61850.
Function block
INDCOMBSPQT
SP_IN*
SP_OUT
TIME*
BLOCKED*
SUBST*
INVALID*
TEST*
IEC15000146.vsd
IEC15000146 V1 EN-US
Figure 170:
INDCOMBSPQT function block
Signals
Table 295:
INDCOMBSPQT Input signals
Name
Type
SP_IN
BOOLEAN
TIME
GROUP
SIGNAL
BLOCKED
BOOLEAN
SUBST
BOOLEAN
INVALID
BOOLEAN
TEST
BOOLEAN
Quantity with cycle time
8 ms
20
Default
Description
0
Single point indication
0
Timestamp
0
Blocked for update
0
Substituted
0
Invalid value
0
Testmode
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
GUID-23D4121A-4C9A-4072-BBE3-6DB076EDAB79 v1
100 ms
100
GUID-13C9325D-D3A0-480F-9F3B-738A13E0ECF8 v3
GUID-EEBD65A5-394C-4ECD-BF6F-D556B610FC57 v3
GUID-55B49FC7-8239-4891-BE16-29296A8F40BE v1
GUID-4543C4C9-FAE2-4328-8DE2-4A5756A020E9 v1
PID-3792-INPUTSIGNALS v2
Technical manual

Advertisement

Table of Contents
loading

Table of Contents