Function Block - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
16.1.3
Phasor measurement unit RES670 2.2 ANSI
Technical manual
I: phase currents (magnitude and angle) (CMMXU)
V: voltages (phase-to-ground and phase-to-phase voltage, magnitude and angle)
(VMMXU, VNMMXU)
The CVMMXN function calculates three-phase power quantities by using fundamental
frequency phasors (DFT values) of the measured current and voltage signals. The
measured power quantities are available either, as instantaneously calculated quantities
or, averaged values over a period of time (low pass filtered) depending on the selected
settings.
It is possible to calibrate the measuring function above to get better then class 0.5
presentation. This is accomplished by angle and magnitude compensation at 5, 30 and
100% of rated current and at 100% of rated voltage.
The power system quantities provided, depends on the actual hardware,
(TRM) and the logic configuration made in PCM600.
The measuring functions CMSQI and VMSQI provide sequence component quantities:
I: sequence currents (positive, zero, negative sequence, magnitude and angle)
V: sequence voltages (positive, zero and negative sequence, magnitude and angle).

Function block

The available function blocks of an IED are depending on the actual hardware (TRM)
and the logic configuration made in PCM600.
Section 16
Monitoring
SEMOD130334-4 v7
489

Advertisement

Table of Contents
loading

Table of Contents