Monitored Data - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

Section 19
Station communication
19.5.5
654

Monitored data

Table 499:
MU1_HW Monitored data
Name
Type
MUDATA
BOOLEAN
SYNCH
BOOLEAN
SMPLLOST
BOOLEAN
MUSYNCH
BOOLEAN
TESTMODE
BOOLEAN
SIMMODE
BOOLEAN
BadReference
BOOLEAN
Derived
BOOLEAN
Failure
BOOLEAN
Inaccurate
BOOLEAN
Inconsistent
BOOLEAN
OldData
BOOLEAN
OperatorBlocked
BOOLEAN
Oscillatory
BOOLEAN
OutOfRange
BOOLEAN
Overflow
BOOLEAN
Source
BOOLEAN
Table continues on next page
Values (Range)
Unit
0=Ok
-
1=Error
0=Ok
-
1=Error
1=Yes
-
0=No
0=Ok
-
1=Error
1=Yes
-
0=No
1=Yes
-
0=No
1=Yes
-
0=No
1=Yes
-
0=No
1=Yes
-
0=No
1=Yes
-
0=No
1=Yes
-
0=No
1=Yes
-
0=No
1=Yes
-
0=No
1=Yes
-
0=No
1=Yes
-
0=No
1=Yes
-
0=No
0=Process
-
1=Substituted
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
PID-6850-MONITOREDDATA v3
Description
Fatal error, data not received,
transmission errors, time-
sync issues or inconsistent
sample rate
Operational mode on
ethernet link
Fatal error or recovery state
after fatal error. High if any
subscribed channel has bad
quality or TEST while IED not
in test mode.
MU not synced or MU clock
not synced to same clock as
IED
Quality of one or more
subscribed analogue
channels is TEST
MU delivers simulated data
accepted by IED
BadReference indication
output for I1
Derived indication output for
I1
Failure indication output for I1
Inaccurate indication output
for I1
Inconsistent indication output
for I1
OldData indication output for
I1
OperatorBlocked indication
output for I1
Oscillatory indication output
for I1
OutOfRange indication output
for I1
Overflow indication output for
I1
Source indication output for
I1
Technical manual

Advertisement

Table of Contents
loading

Table of Contents