Table 691:
IEC Inverse time characteristics for Sensitive directional residual overcurrent and power
protection
Function
Operating characteristic:
æ
ö
A
ç
÷
=
×
t
td
(
)
ç
÷
P
-
è
ø
I
1
EQUATION1653 V1 EN-US
I = I
/I
measured
set
IEC Normal Inverse
IEC Very inverse
IEC Inverse
IEC Extremely inverse
IEC Short time inverse
IEC Long time inverse
Programmable characteristic
Trip characteristic:
æ
ö
A
ç
÷
=
+
×
t
B
td
(
)
ç
÷
P
è
-
ø
I
C
EQUATION1654 V1 EN-US
Reset characteristic:
TR
=
×
t
td
(
)
PR
-
I
CR
EQUATION1655 V1 EN-US
I = I
/I
measured
set
The parameter setting Characterist1 and 4/Reserved shall not be used,
since this parameter setting is for future use and not implemented yet.
Inverse time characteristics
Range or value
0.10 ≤ k ≤ 2.00
1.5 x I
≤ I ≤ 20 x I
set
set
A=0.14, P=0.02
A=13.5, P=1.0
A=0.14, P=0.02
A=80.0, P=2.0
A=0.05, P=0.04
A=120, P=1.0
td = (0.05-999) in steps of 0.01
A=(0.005-200.000) in steps of
0.001
B=(0.00-20.00) in steps of 0.01
C=(0.1-10.0) in steps of 0.1
P=(0.005-3.000) in steps of 0.001
TR=(0.005-100.000) in steps of
0.001
CR=(0.1-10.0) in steps of 0.1
PR=(0.005-3.000) in steps of 0.001
Section 26
Accuracy
IEC 60255-151, ±5.0%
or ±160 ms whichever
is greater
891