Settings - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
15.3.5
Table 240:
TMAGAPC Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
PulseTime
0.050 - 60.000
OnDelay
0.000 - 60.000
OffDelay
0.000 - 60.000
ModeOutput1
Steady
Pulsed
ModeOutput2
Steady
Pulsed
ModeOutput3
Steady
Pulsed
15.3.6
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Name
Type
INPUT30
BOOLEAN
INPUT31
BOOLEAN
INPUT32
BOOLEAN
Table 239:
TMAGAPC Output signals
Name
Type
OUTPUT1
BOOLEAN
OUTPUT2
BOOLEAN
OUTPUT3
BOOLEAN

Settings

Unit
Step
-
-
s
0.001
s
0.001
s
0.001
-
-
-
-
-
-
Operation principle
The trip matrix logic (TMAGAPC) block is provided with 32 input signals and 3
output signals. The function block incorporates internal logic OR gates in order to
provide grouping of connected input signals to the three output signals from the
function block.
Internal built-in OR logic is made in accordance with the following three rules:
Default
Description
0
Binary input 30
0
Binary input 31
0
Binary input 32
Description
OR function betweeen inputs 1 to 16
OR function between inputs 17 to 32
OR function between inputs 1 to 32
Default
Description
Disabled
Operation Disabled/Enabled
0.150
Output pulse time
0.000
Output on delay time
0.000
Output off delay time
Steady
Mode for output ,1 steady or pulsed
Steady
Mode for output 2, steady or pulsed
Steady
Mode for output 3, steady or pulsed
Section 15
Logic
PID-6513-OUTPUTSIGNALS v4
PID-6513-SETTINGS v4
SEMOD52537-5 v8
421