Settings - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
19.8.5
Table 552:
MULTICMDRCV Non group settings (basic)
Name
Values (Range)
tMaxCycleTime
0.050 - 200.000
tMinCycleTime
0.000 - 200.000
Mode
Steady
Pulsed
tPulseTime
0.000 - 60.000
Table 553:
MULTICMDSND Non group settings (basic)
Name
Values (Range)
tMaxCycleTime
0.000 - 200.000
tMinCycleTime
0.000 - 200.000
19.8.6
Phasor measurement unit RES670 2.2 ANSI
Technical manual

Settings

Unit
Step
s
0.001
s
0.001
-
-
s
0.001
Unit
Step
s
0.001
s
0.001
Operation principle
There are 10 instances of the MULTICMDSND function block. The first two are fast
(8 ms cycle time) while the others are slow (100 ms cycle time). Each instance has 16
binary inputs, to which 16 independent signals can be connected. Connected signals are
sent through MULTICMDSND to the receiving equivalent, MULTICMDRCV, located
on a different IED.
The MULTICMDRCV function block has 16 binary outputs, all controlled through the
command block of one or many MULTICMDSND function blocks. There are 60
instances of the MULTICMDRCV where the first 12 are fast (8 ms), and the others are
slow (100 ms). Additionally, the MULTICMDRCV has a supervision function, which
sets the output connector "VALID" to 0 (zero) if its block does not receive any data
within the time defined by tMaxCycleTime.
LON connections are established using LON network tool (LNT).
Station communication
Default
Description
11.000
Maximum cycle time between receptions of
input data
0.000
Minimum cycle time between receptions of
input data
Steady
Mode for output signals
0.200
Pulse length for multi command outputs
Default
Description
5.000
Maximum time interval between transmission
of output data
0.000
Minimum time interval between transmission
of output data
Section 19
SEMOD119927-1 v2
PID-400-SETTINGS v10
PID-399-SETTINGS v10
M14793-3 v3
723