Measured Data - ABB SPEF 3A2 C User Manual And Technical Description

Fault indicator
Table of Contents

Advertisement

Remote reset input
switchgroup SGB

Measured data

Switch
Function
SGB/1
Remote reset of indicators
When SGB/1=0, the indicators are not reset by signal BS.
When SGB/1=1, the indicators are reset by signal BS.
SGB/2
Remote reset of indicators and output relays
When SGB/2=0, the indicators and output relays are not reset by
signal BS.
When SGB/2=1, the indicators and output relays are reset by
signal BS.
SGB/3
Remote reset of indicators, output relays and memorized values.
When SGB/3=0, the indicators, output relays and memorized values
are not reset by signal BS.
When SGB/3=1, the indicators, output relays and memorized values
are reset by signal BS.
SGB/4
Reserved for future use
SGB/5
Reserved for future use
SGB/6
Reserved for future use
SGB/7
Reserved for future use
SGB/8
Reserved for future use
The measured values are shown by the three
right-most digits of the display. The currently
Indicator
Measured data
I
Line current on phase L1 in ampere
L1
I
Line current on phase L2 in ampere
L2
I
Line current on phase L3 in ampere
L3
I
Neutral current in ampere
0
∆I
The actual value of phase unbalance in per cent of the highest phase current
measured data are indicated by an illuminated
LED indicator on the front panel.
Factory
setting
0
0
0
0
0
0
0
0
15