1MRK 511 365-UUS A
16.8
16.8.1
16.8.2
Phasor measurement unit RES670 2.1 ANSI
Technical manual
INPUTn
OUTPUTn
IEC09000732 V1 EN
Figure 217:
BINSTATREP logical diagram
Measured value expander block RANGE_XP
Identification
Function description
Measured value expander block
Functionality
The current and voltage measurements functions (CVMMXN, CMMXU, VMMXU and
VNMMXU), current and voltage sequence measurement functions (CMSQI and VMSQI)
and IEC 61850 generic communication I/O functions (MVGAPC) are provided with
measurement supervision functionality. All measured values can be supervised with four
settable limits: low-low limit, low limit, high limit and high-high limit. The measure value
expander block (RANGE_XP) has been introduced to enable translating the integer
output signal from the measuring functions to 5 binary signals: below low-low limit,
below low limit, normal, above high limit or above high-high limit. The output signals can
be used as conditions in the configurable logic or for alarming purpose.
t
IEC09000732-1-en.vsd
IEC 61850
IEC 60617
identification
identification
RANGE_XP
-
Section 16
Monitoring
t
ANSI/IEEE C37.2
device number
-
573