Mics; Logical Nodes List; Siml-Insulation Medium Supervision (Liquid) - ABB CoreSense M10 User Manual

Multi-gas monitoring system
Hide thumbs Also See for CoreSense M10:
Table of Contents

Advertisement

MICS

Logical Nodes List

The following table contains the list of logical nodes implemented in the device:
L: System Logical Nodes
LPHD (physical device information)
LLN0 (logical node zero)
G: Logical Nodes for Generic References
GGIO (generic process I/O)
S: Logical Nodes for Sensors and Monitoring
SIML (insulation medium supervision [liquid])
SIML–Insulation medium supervision (liquid)
The IEC 61850-7-4 ed.1 SIML node was extended with data objects defined in technical report
IEC 61850-90-4, ed.1.
DO Name
CDC
Lnname
Data Objects
Common Logical Node Information
Mod
inC
Beh
inS
Health
inS
namplt
LpL
Measured Values
H2O
MV
H2OTmp
MV
H2
MV
H2Oppm
MV
H2RoC
MV
MstRoC
MV
CH4
MV
CH4ROC
MV
CO2
MV
CO2ROC
MV
CO
MV
COROC
MV
C2H2
MV
C2H2ROC
MV
C74 User Guide
SIML
Explanation
Shall be inherited from Logical-node Class (see ieC 61850-7-2)
Mode
Behavior
Health
name plate
Relative saturation of moisture in insulating liquid (in %)
Temperature of insulating liquid at point of H₂O measurement
Measurement of hydrogen (in ppm)
Measurement of moisture (in ppm)
Hydrogen rate of change (RoC in ppm/day)
Moisture rate of change (RoC in ppm/day)
Measurement of methane (in ppm)
Methane rate of change (RoC in ppm/day)
Measurement of carbon dioxide (in ppm)
Carbon dioxide rate of change (RoC in ppm/day)
Measurement of carbon monoxide (in ppm)
Carbon monoxide rate of change (RoC in ppm/day)
Measurement of acetylene (in ppm)
Acetylene rate of change (RoC in ppm/day)
M/O/C/E
M
M
M
M
O
O
O
e
e
e
e
e
e
e
e
e
e
e