3.1

SoftGOT-GOT Link Function

3.1.1

SoftGOT-GOT link function setting

The authorization of the SoftGOT-GOT link function can be set, and the exclusive authorization can be obtained or released.
Only the GOT can obtain the exclusive authorization.
While the GOT has the exclusive authorization, GT SoftGOT2000 cannot obtain the authorization.
For the details of the SoftGOT-GOT link function, refer to the following.
Function
Exclusive
The status whether or not the GOT obtains the exclusive authorization is displayed.
authorization
Obtaining or releasing the exclusive authorization can be executed by the GOT.
obtained state
Authorization
The time length from the last operation of GT SoftGOT2000 after obtaining the authorization until the
obtained time
GOT automatically obtains the authorization can be set.
The time period that the authorized equipment (GOT or GT SoftGOT2000) keeps the authorization
Operating priority
after the last operation of the authorized equipment can be set.
guaranteed time
(The unauthorized equipment cannot obtain the authorization until the set time elapses.)
Operation status
When the authorization is not obtained in GT SoftGOT2000/GOT, whether to display or not the
popup notification
information of the authorized side in pop-up can be set.
3.1.2

Display operation of the SoftGOT-GOT link function setting

Special function setting
Touch
[SoftGOT-GOT link function].
3 - 2
3.1 SoftGOT-GOT Link Function
GT SoftGOT2000 Version1 Operating Manual
POINT
POINT
POINT
Relationship with the GOT network interaction function setting
The SoftGOT-GOT link function setting is independent of the GOT network interaction function
setting.
Both of the settings are enabled.
SoftGOT-GOT link function
Description
Setting range
Obtain/Release
<At GOT startup: Release>
0 to 3600 seconds
<At factory shipment: 60
seconds>
0 to 3600 seconds
<At factory shipment: 0
seconds>
YES/NO
<At GOT startup: NO>