Setting Examples In Cqm1/Cqm1H/C200H Series - Mitsubishi Electric F920GOT-K Hardware Manual

Got-f900 series graphic operation terminal
Table of Contents

Advertisement

GOT-F900 SERIES (CONNECTION)
15.4

Setting Examples in CQM1/CQM1H/C200H Series

While referring to the setting examples in the CQM1/CQM1H/C200H Series host link unit, set the
transmission specifications.
The examples below explain the setting in the CQM1/CQM1H (equipped with built-in RS-232C port), the
C200H-LK201-V1 and the C200H-LK202-V1.
1) In the case of CQM1/CQM1H Series (CPU equipped with built-in RS-232C port)
In the CPU CQM1-CPU21/CQM1H-CPU61, execute the setting using the data memory (DM).
Setting item
Setting of standard communication
condition (RS-232C: DN6645)
Setting of communication condition
(RS-232C: DN6646)
Setting of transmission delay time
(RS-232C: DM6647)
Setting of unit number
(RS-232C: DM6648)
Connection of SYSMAC C Series PLC (Manufactured by Omron) 15
Set value
Mode specification: Upper link
0001H
Communication condition: In accordance with DM6646
Transmission format: 7 data bits, 2 stop bits, even parity
0304H
Transmission speed: 19,200 bps
0000H
0 sec
(default status)
××: 2-digit BCD
00××H
(in accordance with the setting on the GOT side)