No.
Message
10000
Command aborted by user
10001
Command timeout.
10002
Bad point file line syntax
10003
Project could not be built.
10004
Cannot initialize Spel class instance.
10005
Cannot initialize parser.
10006
Cannot initialize wbproxy.
10007
Project does not exist.
10008
No project specified.
10009
Cannot open file.
10010
Cannot create file.
10011
File not found
Cannot execute LoadPoints with Robot
10013
Manager open.
Project cannot be locked. It is being
10014
used by another session.
10015
Project could not be synchronized.
10016
Drive not ready
10017
Invalid IP address
10018
Invalid IP mask
10019
Invalid IP gateway
IP address or gateway cannot be the
10020
subnet address.
IP address or gateway cannot be the
10021
broadcast address.
10022
Invalid DNS address
Commands cannot be executed
10023
because the project build is not
complete.
10024
Invalid task name.
10100
Command already in cycle.
10101
Command aborted by user.
10102
Invalid server instance.
10103
Invalid CommandTask value.
Cannot change ServerInstance after
10104
initialized.
10501
Connection aborted.
10502
Cannot connect with the controller.
Controller firmware is not compatible
10503
with this version of RC+.
USB connection of this system is
10504
reserved for the RC620 Controller and
cannot be used for RC+7.0.
The specified connection does not
10505
exist.
10600
Frame grabber driver not installed.
RC700 / RC700-A Rev.23
Maintenance 9. Troubleshooting
Remedy
-
-
-
-
-
-
-
Check whether the project
name and the path are correct.
Specify the project.
Check whether the project
name and the path are correct.
-
Check whether the project
name and the path are correct.
Close the robot manager and
execute.
Terminate other applications.
-
Check whether the drive
designation is correct.
Check the IP address.
Check the IP mask.
Check the IP gateway.
Check the IP address.
Check the IP address.
Check the DNS.
Execute after the project build is
completed.
Check the task name.
-
Execute ResetAbort.
Specify the correct instance.
Specify the correct task
number.
Set ServerInstance before
initialization.
-
-
Upgrade the RC+ version.
Install the RC+7.0 to another
computer.
Check the connection number.
Install the driver.
Note 1
Note 2
297