6.6.2

Connecting to YOKOGAWA PLC (STARDOM)

■1. System Configuration
YOKOGAWA
PLC
Connection cable
Communication
controller
Type
Twisted pair cable
• 10BASE-T
*1
STARDOM
Ethernet
(NFCP100,
NFJT100)
• 100BASE-TX
*1
When connecting STARDOM to MODBUS/TCP, Modbus Communication Portfolio License is required.
For details, refer to the following manual.
*2
When connect a GOT to a PLC, connect to the PCL Ethernet port via a hub.
Use cables, connectors, and hubs that meet the IEEE802.3 10BASE-T/100BASE-TX standards.
*3
When connecting GT2000 to an equipment that meets the 10BASE (-T/2/5) standard, use the switching hub and operate in an
environment where 10Mbps and 100Mbps can be mixed.
*4
A length between a hub and a node.
The maximum distance differs depending on the Ethernet device to be used.
The following shows the number of the connectable nodes when a repeater hub is used.
• 10BASE-T: Max. 4 nodes for a cascade connection (500m)
• 100BASE-TX: Max. 2 nodes for a cascade connection (205m)
When switching hubs are used, the cascade connection between the switching hubs has no logical limit for the number of
cascades.
For the limit, contact the switching hub manufacturer.
*5
Use the straight cable.
Hub
Connection cable
External
Max.
device
*5
Cable model
*4
distance
Shielded
twisted pair
cable (STP) or
unshielded
twisted pair
cable (UTP):
100m
Hub
Category 3, 4,
and 5
Shielded
twisted pair
cable (STP):
Category 5 and
5e
YOKOGAWA PLC user's Manual
GOT
Connection cable
Connection cable
Max.
*5
Cable model
*4
distance
Twisted pair cable
• 10BASE-T
Shielded
twisted pair
cable (STP) or
unshielded
twisted pair
cable (UTP):
*2
100m
Category 3, 4,
and 5
• 100BASE-TX
Shielded
twisted pair
cable (STP):
Category 5 and
5e
6.6 Example of Connection
Communication driver
MODBUS/TCP Master, Gateway
*3
GOT
Number of
connectable
GOT
Option device
equipment
Model
126 GOTs
- (Built into GOT)
for 1 PLC
6
6 - 15