Connecting Freqrol-F700/F700P Series - Mitsubishi Electric GT16 User Manual

Got1000 series
Hide thumbs Also See for GT16:
Table of Contents

Advertisement

24.5.8 Connecting FREQROL-F700/
F700P series
Communication settings
Make the communication settings of the inverter.
Be sure to perform the inverter reset after updating
each parameter.
(1) Communication port and corresponding parameters
GOT connection
Parameters corresponding to inverter
destination
PU connector
Pr.79, Pr.117 to Pr.124, Pr.340, Pr.342
RS-485 terminal
Pr.79, Pr.331 to Pr.337, Pr.340 to Pr.342, Pr.549
(2) Communication settings of inverter
Set the following parameters using the PU (parameter
unit). Set Pr.160 (User group read selection) to 0 [The
simple mode and extended parameters can be
displayed] before making the parameter settings.
Do not change these parameters, even though they
can be monitored from the GOT. If they are changed,
communication with the GOT is disabled.
Parameter No.
*1
Setting item
PU
connector
PU communication
station number
/RS-485
Pr.117
communication station
number
PU communication
speed
Pr.118
/RS-485
communication speed
*2
PU communication
stop bit length
/
Pr.119
RS-485
communication stop bit
*2
length
PU
communication parity
check
/
Pr.120
RS-485
communication parity
*2
check
Number of
PU communication
retries
Pr.121
/
RS-485 communication
retry count
PU communication
check time interval
/
Pr.122
RS-485 communication
check time interval
PU communication
waiting time setting
/
Pr.123
RS-485 communication
waiting time setting
PU communication
CR/LF selection
/
Pr.124
RS-485 communication
CR/LF selection
Protocol selection
-
24 - 20
24. INVERTER CONNECTION
24.5 FREQROL Series Inverter Side Settings
Contents of
Set value
RS-
setting
485
Pr.331
0 to 31
24.5.13 Station
number setting
*4
Pr.332
19200bps
192
Data length: 7bit
Pr.333
10
Stop bit length:
1bit
Pr.334
1
Odd
The inverter will
Pr.335
9999
not come to an
alarm stop.
Communication
*4
Pr.336
9999
check suspension
Pr.337
0
0ms
With CR
*3
Pr.341
1
Without LF
Mitsubishi inverter
*3
Pr.549
0
protocol
Parameter No.
*1
Setting item
PU
connector
Operation mode
Pr.79
selection
Communication startup
Pr.340
mode selection
Communication
EEPROM
Pr.342
write selection
*1
Setting items are parameter names described in the manual
of FREQROL-F700 series.
*2
Settings on the GOT can be changed.
When changing the settings on the GOT, be sure to change
the parameters on the inverter to correspond with the GOT
settings.
*3
Inverter default values (No need to change)
*4
Since the value has been set as a default, no setting is
required when connecting to the PU connector on the
inverter side.
HINT
HINT
HINT
Automatic setting with Pr.999 (FREQROL-F700P
series only)
If Pr.999 is set as the following, the communication
settings other than [PU communication station
number] and [Communication EEPROM write
selection] can be automatically set in a batch to the
default communication settings of the GOT side.
Parameter
Set
Contents of setting
No.
value
GOT Initial settings
10
(PU connector)
*1
Pr.999
GOT Initial settings
11
(RS-485 terminal)
*1
When monitoring the value of Pr.999, 9999 is always
monitored.
Contents of
Set value
RS-
setting
485
PU
PU operation
1
connector
mode
External operation
0
RS-485
mode at power on
*3
PU
Refer to
0
connector
Pr.79 settings.
*3
Network operation
RS-485
1
mode.
Written to RAM
*3
0
and EEPROM
Operation in parameter
setting mode
[AUTO]
[GOT]
[1]Write
-