Remedy:
- check the required interface configuration (p8920 and following), correct if necessary, and activate (p8925).
or
- reconfigure the station via the "Edit Ethernet node" screen form (e.g. with STARTER commissioning software).
See also: p8925 (Activate PN interface configuration)
F08700 (A)
CAN: Communications error
Message class:
Communication error to the higher-level control system (9)
Reaction:
OFF3 (NONE, OFF1, OFF2)
Acknowledge:
IMMEDIATELY
Cause:
A CAN communications error has occurred.
Fault value (r0949, interpret decimal):
1: The error counter for the send telegrams has exceeded the BUS OFF value 255. The bus disables the CAN
controller.
- bus cable short circuit.
- incorrect baud rate.
- incorrect bit timing.
2: The master no longer interrogated the CAN node status longer than for its "life time". The "life time" is obtained
from the "guard time" (p8604[0]) multiplied by the "life time factor" (p8604[1]).
- bus cable interrupted.
- bus cable not connected.
- incorrect baud rate.
- incorrect bit timing.
- master fault.
Note:
The fault response can be set as required using p8641.
See also: p8604 (CAN life guarding), p8641 (CAN Abort Connection Option Code)
Remedy:
- check the bus cable
- check the baud rate (p8622).
- check the bit timing (p8623).
- check the master.
The CAN controller must be manually restarted with p8608 = 1 after the cause of the fault has been resolved!
See also: p8608 (CAN Clear Bus Off Error), p8622 (CAN bit rate), p8623 (CAN Bit Timing selection)
F08701
CAN: NMT state change
Message class:
Communication error to the higher-level control system (9)
Reaction:
OFF3
Acknowledge:
IMMEDIATELY
Cause:
A CANopen NMT state transition from "operational" to "pre-operational" or after "stopped".
Fault value (r0949, interpret decimal):
1: CANopen NMT state transition from "operational" to "pre-operational".
2: CANopen NMT state transition from "operational" to "stopped".
Note:
In the NMT state "pre-operational", process data cannot be transferred and in the NMT state "stopped", no process
data and no service data can be transferred.
Remedy:
Not necessary.
Acknowledge the fault and continue operation.
F08702 (A)
CAN: RPDO Timeout
Message class:
Communication error to the higher-level control system (9)
Reaction:
OFF3 (NONE, OFF1, OFF2)
Acknowledge:
IMMEDIATELY
Cause:
The monitoring time of the CANopen RPDO telegram has expired because the bus connection was either interrupted
or the CANopen Master was switched-off.
See also: p8699 (CAN: RPDO monitoring time)
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
4 Faults and alarms
4.2 List of faults and alarms