Siemens SINAMICS S110 List Manual page 60

Hide thumbs Also See for SINAMICS S110:
Table of Contents

Advertisement

Parameter
List of parameters
This assignment is made using the unique component number that was assigned when parameterizing the topol-
ogy.
Only component numbers can be entered into this parameter that correspond to an encoder.
Note:
If the encoder evaluation and encoder are integrated (motor with DRIVE-CLiQ), then their component numbers are
identical.
For an SMC, different component numbers are assigned for the SMC (p0141) and the (actual) encoder (p0142).
p0144[0...n]
Sensor Module detection via LED / SM detection LED
SERVO_S110-CAN,
Can be changed: U, T
SERVO_S110-DP,
Data type: Unsigned8
SERVO_S110-PN
P-Group: Encoder
Not for motor type: -
Min
0
Description:
Detects the Sensor Module assigned to this drive and data set.
Note:
While p0144 = 1, the READY LED flashes green/orange or red/orange with 2 Hz at the appropriate Sensor Module.
p0145[0...n]
Activate/de-activate encoder interface / Enc_intf act/deact
SERVO_S110-CAN,
Can be changed: C1(4), U, T
SERVO_S110-DP,
Data type: Integer16
SERVO_S110-PN
P-Group: Data sets
Not for motor type: -
Min
0
Description:
Setting to activate/de-activate an encoder interface (Sensor Module).
Value:
0:
1:
2:
Recommend.:
After inserting a component, before activating, first wait for Alarm A01317.
Dependency:
Refer to: r0146
Refer to: A01314, A01317
Note:
The de-activation of an encoder interface corresponds to the"parking encoder" function and has the same effect.
The activation of a component can be rejected if the component was inserted for the first time.
In this case, it is only possible to activate the component when the pulses for all of the drive objects are inhibited.
With the encoder interface for encoder 1 (motor encoder), the relevant drive object for writing the parameter must
be in the "Ready for operation" state.
With the encoder interface for encoders 2 and 3, the parameter can also be written during operation.
Re value = 0, 2:
When a component is deactivated it no longer outputs any errors.
If value = 0:
The component was completely commissioned and is deactivated using this value. It can be removed from the
DRIVE-CLiQ without any error.
If value = 1:
The component must be available for error-free operation.
If value = 2:
A component in a project generated offline and set to this value must never be inserted in the actual topology from
the very start.
For components that comprise several individual components (e.g. Double Motor Modules), it is not permissible to
set just one subset to this value.
1-60
De-activate component
Activate component
Component, de-activate and not present
Calculated: -
Dynamic index: EDS, p0140
Units group: -
Scaling: -
Max
1
Calculated: -
Dynamic index: EDS, p0140
Units group: -
Scaling: -
Max
2
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents