M4M 20 NETWORK ANALYZER USER MANUAL

3.6.Technical data

Auxiliary power supply
Voltage range
Frequency
Power consumption
Installation category
Protection fuse
Measurement accuracy
Measurement type
IEC 61557-12
Active energy
Reactive energy
Active power
Reactive power
Apparent power
Voltage
Current
Neutral current
Frequency
Unbalances
Harmonics, THD (Current, voltage)
Voltage measurement inputs
Measurement range
Measurement category
Rated frequency
Max. VT secondary (indirect connection)
Max over voltage
Protection fuse
The M4M voltage inputs have a high impedance which decreases power consumption and increases
security due low current flow in the voltage input circuit. However, if the voltage input wirings are
floating, i.e. not connected to a voltage source, the wires may work as an antenna to the surroundings
electric fields which can create a perceived floating voltage. The M4M will not show this floating voltage
in case it is below 40V (below the Voltage measurement range) and in case of a three phase system
with measuring current below starting current (below current measurement range). In all other cases
of floating voltage the M4M display may show a voltage bigger than zero, which depends on installation
conditions. This behavior does not affect the reliability of the M4M in normal conditions with a connected
load.
[V]
48 to 240 VAC/VDC ±15%
[Hz]
50/60 Hz ±5%
[VA]
10 VA max
CAT III 300V class per IEC 61010-1 edition 3
T1 A - 277 VAC
True RMS up to the 40th harmonic
128 samples per cycle, zero blind
IEC 61557-12 PMD/S/K70/0,5
Class 0,5 acc. to IEC 61557-12
Class 0,5S acc. to IEC 62053-22
Class 2 acc. to IEC 61557-12
Class 2S acc. to IEC 62053-23
Class 0,5 acc. to IEC 61557-12
Class 2 acc. to IEC 61557-12
Class 0,5 acc. to IEC 61557-12
Class 0,2 acc. to IEC 61557-12
Class 0,2 acc. to IEC 61557-12
Calculated
Class 0,1 acc. to IEC 61557-12
Class 0,2 acc. to IEC 61557-12
Class 1 acc. to IEC 61557-12
[V]
46(80)...480(830) V
400V~ (CAT III)
[Hz]
50-60 Hz
[V]
400 VAC (L-N)
[V]
800 VAC (L-L)
[V]
T1 A - 277 VAC
11