Specification Of Circuit Breaker And Fuse - Delta ASD-A2 Series User Manual

Table of Contents

Advertisement

Chapter 2 Installation

2.5 Specification of Circuit Breaker and Fuse

220V Series
Caution: Please use the fuse and circuit breaker that is recognized by UL/CSA.
Servo Drive Model
Operation Mode
ASD-A2-0121-
ASD-A2-0221-
ASD-A2-0421-
ASD-A2-0721-
ASD-A2-1021-
ASD-A2-1521-
ASD-A2-2023-
ASD-A2-3023-
ASD-A2-4523-
ASD-A2-5523-
ASD-A2-7523-
ASD-A2-1B23-
ASD-A2-1F23-
If the servo drive equips with earth leakage circuit breaker for avoiding electric
NOTE
leakage, please choose the current sensitivity which is over 200 mA and can
continue up to 0.1 seconds.
400V Series
Caution: Please use the fuse and circuit breaker that is recognized by UL/CSA.
Servo Drive Model
Operation Mode
ASD-A2-0743-
ASD-A2-1043-
ASD-A2-1543-
ASD-A2-2043-
ASD-A2-3043-
ASD-A2-4543-
ASD-A2-5543-
ASD-A2-7543-
If the servo drive equips with earth leakage circuit breaker for avoiding electric
NOTE
leakage, please choose the current sensitivity which is over 200 mA and can
continue up to 0.1 seconds.
Revision February, 2017
Circuit Breaker
General
5A
5A
10A
10A
15A
20A
30A
30A
70A
75A
95A
-
-
Circuit Breaker
General
10A
15A
20A
30A
30A
70A
75A
95A
ASDA-A2
Fuse (Class T)
General
5A
5A
10A
20A
25A
40A
50A
70A
140A
150A
175A
-
-
Fuse (Class T)
General
20A
25A
40A
50A
70A
140A
150A
175A
2-5

Hide quick links:

Advertisement

Table of Contents
loading